CME-7001/7002 Auxiliary Switches 1 Installation Guide
Installation Guide
Auxiliary Switches
CME-7001/7002
Mounting 1
Wiring and Dimensions 2
Maintenance 2
Important Notices 2
Specifications 2
Mounting
These auxiliary switches are designed to start and
stop auxiliary items or to indicate an actuators fully
open or closed position. The single or dual switch
models are fully adjustable over the actuators 0 to
90° rotation. Switches are independently adjustable
for a trip point anywhere within the angular rotation
of the driving actuator.
They are designed to mount on any KMC MEP-7000
Series Actuator as described here:
1. Insertthe“D”sha,foundontheundersideof
theswitchbox,intothe“D”hubontopofthe
actuator cover.
2. Fasten the switch box to the actuator with 4
screws (provided). This requires punching the
screws through the label on the actuator cover.
3. Depressthegeardisengagementbuon(red)and
rotate the actuator fully counterclockwise (CCW).
4. Loosen the center screw on the switch dial.
5. Turn the switch dial until the arrow on the dial
is pointing at the desired switching point on the
scale.
6. Tighten the center screw on the switch dial to lock
the switching position.
7. Verify the correct switching point by manually
rotating the actuator. The switch dial is
mechanically coupled to the actuators gear train
and will follow the actuators rotation. The switch
operates each time the arrow on the switch dial
passes “0” or “90” on the scale.
8. See the Wiring and Dimensions section on the
next page.
“D” Shaft
Screws
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - Installation Guide

CME-7001/7002 Auxiliary Switches 1 Installation GuideInstallation GuideAuxiliary SwitchesCME-7001/7002 Mounting 1Wiring and Dimensions 2Maintenan

Pagina 2 - Wiring and Dimensions

CME-7001/7002 Auxiliary Switches 2 Installation Guide© 2009 KMC Controls, Inc. 826-019-02BImportant NoticesThe material in this document is for i

Modelos relacionados CME-7001

Comentarios a estos manuales

Sin comentarios