Kmc-controls CCC-1002 Manual de usuario

Busca en linea o descarga Manual de usuario para Sensores Kmc-controls CCC-1002. KMC Controls CCC-1002 User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 4
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
CCC-1001/1002 (Dual Input Receiver Controllers) 1 Installation Guide
ConnectionsMounting
Installation Guide
Dual Input Receiver Controllers
CCC-1001/1002
The CCC-1001 and CCC-1002 are not position sensi-
tive, but they must be calibrated and mounted in the
same orientation.
1. Locate the three mounting ears (anges) on the
unit.
2. Place the controller on the mounting surface and
mark the locations of the two top ears.
3. Partially install two mounting screws (#8 or #10)
on the marks. These should be 3-1/2" (89 mm)
apart.
4. Slide the top ears under the screws.
5. Install the third mounting screw in the boom ear
and tighten all three screws.
The units are supplied as Direct Acting (DA). If
Reverse Acting (RA) is required:
1. Locate the tubing connections on the back of the
controller.
2. Cut the branch tubing at the DA connection
(lower right corner).
3. Remove tubing from the two-prong guides.
4. Connect branch tubing to the RA connection
(upper right corner) using brass ings
(provided).
5. Secure extra tubing in the two-prong guides.
A CCC-1001/1002 controller has ve 3/16" (5 mm)
ports to accept 1/4" (6 mm) O.D. polyethylene tubing.
Connect the controller to other units as follows:
1. Main control air to Port M. This should be 20 psig
(137 kPa), 30 psig (207 kPa) max.
2. Primary input, 3–15 psig, to Port 1.
3. Remote setpoint adjustment, 3–15 psig with a +/–
10% oset, to Port 2.
4. Secondary input to Port 3.
CCC-1001 Shown
M
M
M
M
Primary Transmitter
(sensed medium, e.g., hot water)
Restrictor
Restrictor
Optional Secondary Transmitter
(sensed medium, e.g., outside air)
Optional Remote
Setpoint Adjust
Regulator
Controlled
Device
Primary Input: 1
Output Signal: B
Main Air: MAIN
Secondary Input: 3
Remote Setpoint: 2
CAUTION
Pneumatic devices must be supplied with clean, dry
control air. Any other medium (e.g., oil or moisture
contamination) will cause the device to fail.
Mounting 1
Connections 1
Adjustments and Calibration 2
CCC-1001 Controller 2
CCC-1002 Controller 2
Throttling Range Adjustment 2
Authority Calibration 2
Setpoint Calibration 3
Remote Setpoint Adjustment 3
Accessories 3
Maintenance 3
Competitor Cross-Reference 4
CCC-1001 =
2-3/16" (56 mm);
CCC-1002 =
2-5/16" (59 mm)
Vista de pagina 0
1 2 3 4

Indice de contenidos

Pagina 1 - Installation Guide

CCC-1001/1002 (Dual Input Receiver Controllers) 1 Installation GuideConnectionsMountingInstallation GuideDual Input Receiver ControllersCCC-1001/100

Pagina 2 - Adjustments and Calibration

CCC-1001/1002 (Dual Input Receiver Controllers) 2 Installation GuideAuthority CalibrationThis adjustment determines the eect of a secondary transmi

Pagina 3 - Accessories

CCC-1001/1002 (Dual Input Receiver Controllers) 3 Installation GuideSetpoint CalibrationInitial setpoint calibration is done aer the spring tube on

Pagina 4 - Competitor Cross-Reference

CCC-1001/1002 (Dual Input Receiver Controllers) 4 Installation Guide© 2009 KMC Controls, Inc. 218-019-01EKMC Controls, Inc.19476 Industrial Drive

Modelos relacionados CCC-1001

Comentarios a estos manuales

Sin comentarios