Installation Guide
Dual Temperature Room Thermostat
CTE –1005, 1008, 1105, 1108
Mounting
Standard:
The base unit’s mounting slots are designed to align with the
holes in a standard 2" x 4" (51x102) handy conduit box.
Use a 2" (51) deep box if using conduit.
Normal screw and anchor systems may be used on solid
walls.
Hollow wall:
1. Cut a 3-3/4" x 1-3/4" rectangular opening in the wall.
(Check if unit is horizontal or vertical before cutting)
2. Make all necessary connections
3. Insert Toggle Bolt Assembly (HMO-5001, ordered separately)
through the wall and tighten.
Care should be taken not to bend or flex the base of the
thermostat.
Required Tools
• digital voltmeter
• small phillips screwdriver
• small flatblade screwdriver
• keyhole saw
Wiring
Typically, T1 and T3 are used for cooling and T2
and T4 are used for heating. Refer to the wiring
diagram.
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - Installation Guide

Installation GuideDual Temperature Room ThermostatCTE –1005, 1008, 1105, 1108MountingStandard:• The base unit’s mounting slots are designed to align w

Pagina 2 - Maintenance

KMC ControlsP.O. Box 49719476 Industrial DriveNew Paris, IN 46553U.S.A.TEL: 574.831.5250FAX: 574.831.5252E-mail: [email protected]

Modelos relacionados CTE–1105 | CTE–1008 | CTE–1005 |

Comentarios a estos manuales

Sin comentarios