Installation Guide
Carbon Monoxide (CO) Detectors
SAE-1101, 1102 , 1151, 1152
Mounting
SAE-1101 and 1102 Space Mount
Install the unit at least five feet from floor of the area to be
controlled. Do not install doors, opening windows,
supply air diffusers of other known air disturbances.
1. Remove the cover by loosening, and removing, the
screws located at the corners of the cover.
2. Remove a knockout from the top or bottom for
wiring.
3. Attach the unit directly on a standard electrical box
or directly to a wall using the existing holes.
Complete wiring per Wiring Section and replace cover.
SAE-1151 and 1152 Duct Mount:
Choose a mounting location in a straight section of a
return air duct. Mount at least 5 feet from corners and
other items that may cause disturbances in the air flow. Avoid vibration areas or areas of rapid
temperature change.
1. Cut a 3/4" hole in duct for the air sampling tube.
2. Remove the cover by loosening, and removing, the screws located at the corners of the
cover.
3. Remove a knockout from top or bottom for wiring.
4. Insert sampling tube into the duct and use the foam plug (included) to prevent air
infiltration.
5. Center the sensor over the hole in th eductwork .
6. Attach the unit to the ductwork by threading four screws through the self-sealing rubber
gaskets on the back of the housing.
Complete wiring per Wiring Section and replace cover.
Wiring
Use 22 AWG shielded wiring for all connections. Do not locate device wires in the same
conduit with wiring used to supply inductive loads.
1. Connect the positive DC voltage or the hot side of the AC voltage to the terminal
marked PWR.
2. Connect the power supply common to the terminal marked COM. This device is
reverse voltage protected and will not operate if connected backwards
Vista de pagina 0
1 2 3 4 5 6 7 8

Indice de contenidos

Pagina 1 - Installation Guide

Installation GuideCarbon Monoxide (CO) DetectorsSAE-1101, 1102 , 1151, 1152MountingSAE-1101 and 1102 Space MountInstall the unit at least five feet f

Pagina 2 - Wiring Continued

NOTE: The Detector has a half-wave type power supply. The power supply common isthe same as the output signal common. Therefore, several units may b

Pagina 3

Direct Digital Controller24 VAC– + +24 VDC+ + –Direct Digital Controller24 VDC+ + –– + +Direct Digital Contr

Pagina 4 - Operation

Start-Up1. Verify that the Carbon Monoxide Transmitter is proplerly wired and all connections are tight.2. Apply power. A 200 second warm-up period

Pagina 5 - Menu Configuration

Menu ConfigurationMenu is controlled by using the four buttons on the circuit board (MENU, SAVE, UP and DOWN). Press<MENU> to step through the

Pagina 6 - Menu Configuration Continued

Menu Configuration ContinuedPress <MENU>9. RELAY 2 DEL=2MIND11 and D12 flash three times to indicate thismode.No LEDs lit = 0 minutesD9 lit = 1

Pagina 7

TestA special test menu that can be used during setup isavailable by temporarily shorting pins 1 and 2 on J4on the Printed Circuir Board.Short 1-2 on

Pagina 8 - Maintenance

717-019-38KMC ControlsP.O. Box 49719476 Industrial DriveNew Paris, IN 46553U.S.A.TEL: 574.831.5250FAX: 574.831.5252E-mail: [email protected] Main

Comentarios a estos manuales

Sin comentarios