FlexStat 1 Operation Guide, Rev. ROperation GuideFlexStat™BACnet Programmable ThermostatsContentsOverview ...
FlexStat 10 Operation Guide, Rev. RSetback (OAT) Lockout Setup SETBACK LOCKOUTOAT LOCKOUT:LOCKOUT TEMP: 30° FENABLESetback OAT lockout is disabled b
FlexStat 11 Operation Guide, Rev. R(Advanced) CO2 Sensor (and DCV) CO2 SENSORSENSOR INFOCALIBRATION CO2 SENSOR INFOMODEL: T6615SUB VOL: A15SW DATE:
FlexStat 12 Operation Guide, Rev. RNOTE: Not all applications have a modulating economizer option. Withoutamodulatingeconomizerselected,DCVwil
FlexStat 13 Operation Guide, Rev. Rposition, not the minimum outside air percentage.) The OA damper shall be at this position when Space CO2 is at or
FlexStat 14 Operation Guide, Rev. Rnished and returned the ventilation rate to “normal” operation).• Pre-purge—If enabled in the programming (disab
FlexStat 15 Operation Guide, Rev. RRoute StatusStatus Description ActionActive The network is functioning correctly and capable of passing traffic.Non
FlexStat 16 Operation Guide, Rev. R(Advanced) Date/Time DATE/TIMEDATE:TIME: 1:43:59 PMUTC OFFSET: 300DST ENABLE: TRUEDST AUTO: TRUEDST START:>2ND
FlexStat 17 Operation Guide, Rev. R(Advanced) BACnet Device Properties DEVICEINSTANCE:NAME: FlexStat_101LOCATION: KMC Controls1To set the BACnet devi
FlexStat 18 Operation Guide, Rev. R(Advanced) PID Loop Configuration LOOP CONFIGURATIONCOOL PROP:HEAT PROP: 2.0° FCOOL INTG: 0/hrHEAT INTG: 0/hrECON
FlexStat 19 Operation Guide, Rev. R(Advanced) Test TESTLCD/KEY TESTThe test menu merely tests the display’s pixels and key functions (as verication
FlexStat 2 Operation Guide, Rev. RResetting the FlexStat ...26Types of Reset ...
FlexStat 20 Operation Guide, Rev. R(Advanced) Trend Logs TREND LOGSTREND 1:TREND 2: TRUETREND 3: FALSETREND 4: FALSETREND 5: FALSETREND 6: FALSETREN
FlexStat 21 Operation Guide, Rev. R(Advanced) User Interface (UI) USER INTERFACECONTRASTDISPLAY BLANKING: NOINACTIVITY (SECS): 60ROTATION VALUESSHOW
FlexStat 22 Operation Guide, Rev. RFor Hospitality mode, Setpoint Control conguration options are Single Setpoint or Schedule:• SingleSetpoint wil
FlexStat 23 Operation Guide, Rev. RAlarms SAT 4/11 3:20 PM COOL: OCC: FAN: SERVICE HUM: 20%R
FlexStat 24 Operation Guide, Rev. RSchedules SCHEDULEENTIRE WEEK [MON–SUN]WEEKDAYS [MON–FRI]WEEKEND [SAT–SUN]INDIVIDUAL DAYSHOLIDAYS ENTIRE WEEK1:2:
FlexStat 25 Operation Guide, Rev. RSystem Modes SYSTEMSYSTEM ENABLE:OCC OVRIDE (HRS): 1.0AUTOThis menu allows changes to system enable (auto, o, hea
FlexStat 26 Operation Guide, Rev. RTrend Viewer TREND VIEWER1:2: SPACE HUMIDITY 273: FAN 194: COOL 1 185: COOL 2 2
FlexStat 27 Operation Guide, Rev. RA coldstart does the following in the FlexStat:• (Afterzeroingoutobjectsduringtherestartprocess)returns
FlexStat 28 Operation Guide, Rev. RMS/TP Network CommunicationConnect the EIA-485 MS/TP network wiring and set the EOL switches accordingly. (See the
FlexStat 29 Operation Guide, Rev. RFirmware UpgradeThe existing version of rmware can be viewed from the About the FlexStat screen. (See About the F
FlexStat 3 Operation Guide, Rev. ROverview Applications and Installation1. Wire the FlexStat’s backplate to the desired equipment and set the FlexS
FlexStat 30 Operation Guide, Rev. RTroubleshootingAlarm IssuesAlarm, (False) Fan Fail• Check conguration. Be sure the Fan Status option is not sele
FlexStat 31 Operation Guide, Rev. R• Reduce the Max Master number down to the minimum needed for that network—see (Ad-vanced) Communications (BACnet
FlexStat 32 Operation Guide, Rev. RDisplay Is Blank (or Erratic)• If the display comes on when a buon is pushed, Display Blanking is enabled. (See
FlexStat 33 Operation Guide, Rev. RCustom Programming and Web IssuesControl Basic Programs Do Not WorkNOTE: The FlexStat has a library of built-in a
FlexStat 34 Operation Guide, Rev. RCO2 Level Is “Too High”• See the CO2 and DCV Sequences Are Not Work-ing section above.• To reduce nuisance compl
FlexStat 35 Operation Guide, Rev. RAlso check that its leads are not pinched, shorted, or broken and that the tape holding down the leads is not loos
FlexStat 36 Operation Guide, Rev. ROutput, Fan, and Relay IssuesAnalog Output Does Not Work CAUTIONDo not mistakenly connect 24 VAC to an analog outp
FlexStat 37 Operation Guide, Rev. RRelay (Internal) Does Not Work CAUTIONRelays are for Class-2 voltages (24 VAC) only. Do not connect line voltage t
FlexStat 38 Operation Guide, Rev. R• If the USBportdoesnotappearinthedrop-downlist, close the tool, remove power to the FlexStat, disconnect
FlexStat 39 Operation Guide, Rev. RWiring IssuesInstallation Wiring Considerations CAUTIONTo avoid damage from ground loops and other communication i
FlexStat 4 Operation Guide, Rev. ROperation (Basic)NavigationNavigatethemenusandchangeseingsbypress-ingacombinationofvariousarrowbuon
FlexStat 40 Operation Guide, Rev. RImportant NoticesThe KMC logo and TotalControl are registered trademarks and BACstage is a trademark of KMC Contro
FlexStat 41 Operation Guide, Rev. RReferenceCommonacronymsandabbreviations in FlexStat and related documents include:amp = amperesA = amperesAAC =
FlexStat 42 Operation Guide, Rev. RFor denitions of various terms in this document, refer to the award-winning pocket-sized GreenBuildingandCon-t
FlexStat 43 Operation Guide, Rev. RIndexAAbbreviations: 41About the FlexStat: 6Access Levels, Password: 18Accessories: 29Acronyms: 41Adapter Bac
FlexStat 44 Operation Guide, Rev. RDetector. See Motion SensorDeviceInstance: 6, 17, 27, 28Properties: 17Diagnostics, MS/TP: 15Differential, Minim
FlexStat 45 Operation Guide, Rev. RPParts (Accessories): 29Passwords: 18, 25PC (Network) Data Port: 28PECI (Portland Energy Conservation, Inc.):
FlexStat 46 Operation Guide, Rev. R© 2014 KMC Controls, Inc. 913-019-02RKMCControls19476 Industrial DriveNew Paris, IN 46553574.831.5250; Fax 574.
FlexStat 5 Operation Guide, Rev. R WED 11/19 3:22 PM COOL: OCC: FAN: HUM: 37%
FlexStat 6 Operation Guide, Rev. RConfiguration (Setup)NOTE: MenusshowninthisdocumentreectFIRMWAREVERSIONR2.1.0.9orlater.Actualcontext-
FlexStat 7 Operation Guide, Rev. RAdvanced Menu ADVANCEDAPPLICATIONCB PROGRAMSCOMMUNICATIONDATE/TIMEDEVICEINPUTSLIMITSThe Advanced Menu displays var
FlexStat 8 Operation Guide, Rev. RWhen BAC-1xxxxx models have an application with the CO2 sensor ANDthemodulatingeconomizeroptionenabled, menu
FlexStat 9 Operation Guide, Rev. Rreverting from Standby back to Occupied mode (although it may still take some time for the room to reach its norma