SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors 1 Installation Guide
Installation Guide
Carbon Monoxide (CO) Detectors
SAE-1101/1102/1151/1152
SAE-1101/1102 Space Mount
Install the unit at least ve feet above the nished oor
of the area to be controlled. Do not install near doors,
windows, supply air diffusers of other knownair
disturbances. Avoid areas prone to vibration or rapid
temperature change.
1. Remove the cover by loosening and removing the
four screws.
2. Remove a knockout from the top or boom for
wiring.
3. Aach the universal backplate directly to a
standard electrical box using two screws.
4. Aer wiring, conguring, and testing the unit,
reinstall the cover.
SAE-1151/1152 Duct Mount
Choose a mounting location in a straight section of
a return air duct. Mount at least 5 feet (or 7.5 duct
diameters) from corners and other items that may
cause disturbances in the air ow. Avoid areas prone
to vibration or rapid temperature change.
1. Cut a 1
1
8-inch hole in the duct for the air sampling
tube.
2. Remove the cover by loosening and removing the
four screws.
3. Remove a knockout from the top or boom for
wiring.
4 . Insert the sampling tube into the duct. Use the
foam plug (included) to prevent air from entering
the enclosure, causing false readings.
5. Centering the sensor over the hole in the
ductwork, aach the unit to the ductwork by
threading four screws through the self-sealing
rubber gaskets on the backplate of the housing.
6. Aer wiring, conguring, and testing the unit,
reinstall the cover.
Mounting
Accessories
IEI-1001 LCD Display Module
(required for congu-
ration)
XEE-6111-040 Transformer, 120-
to-24 VAC, 40 VA,
single-hub
XEE-6112-040 Transformer, 120-to-
24 VAC, 40 VA, dual-
hub
4.9" W (124 mm)
7.22" H
(183 mm)
1.69" D (43 mm)
or
9.9" D (250 mm)
with duct
insertion tube
Models
SAE-1101 Space CO sensor (aer 5/2007)
SAE-1102 Space CO sensor with two relays
and audible alarm (aer 2/2007)
SAE-1151 Duct CO sensor (aer 12/2006)
SAE-1152 Duct CO sensor with two relays
and audible alarm (aer 11/2004)
NOTE: These instructions apply to units
manufactured aer the corresponding
dates shown in the Models list. For older
units (with a row of LEDs on the le side
of the board), see the original version of
this installation guide available on www.
kmccontrols.com.
Vista de pagina 0
1 2 3 4 5

Indice de contenidos

Pagina 1 - Installation Guide

SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors 1 Installation GuideInstallation GuideCarbon Monoxide (CO) Detectors SAE-1101/1102/1151/1152

Pagina 2 - CAUTION

SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors 2 Installation GuideUse 22 AWG shielded wiring for all connections. Do not locate device wire

Pagina 3 - Operation

SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors 3 Installation GuideSet-UpWarm-Up1. Verify that the detector is properly wired and all conne

Pagina 4

SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors 4 Installation GuideNormal (Configuration) Menu PressandreleasetheMENUbuontoenterthe

Pagina 5 - Calibration

SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors 5 Installation GuideSpecificationsRange 0–300 ppmAccuracy and Operation Conditions ±3% of rea