SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 1 Installation Guide
Installation Guide
Carbon Monoxide (CO) Detectors
SAE-1111/1112/1162
Mounting 1
SAE-1111/1112 Space Mount 1
SAE-1162 Duct Mount 1
Wiring 2
Operation 3
Warm-Up Mode 3
Normal Mode 3
Alarm Mode 3
Configuration 4
Test Mode 4
Fault Mode 4
ReCal (Recalibration) Mode 4
Calibration 8
Models 9
Accessories 9
Maintenance 9
Important Notices 9
More Information 9
SAE-1111/1112 Space Mount
Install the unit at least ve feet above the nished
oor of the area to be controlled. Do not install
near doors, windows, supply air diusers of other
known air disturbances. Avoid areas prone to vibra-
tion or rapid temperature change.
1. On the mounting surface, mark and drill the four
mounting holes (for screws) and remove any
debris from all holes.
2. Aach the unit to the surface by threading four
screws through the four mounting holes.
3. Remove the two cover screws (if installed),
release the latch, and swing open the cover.
4. Insert wiring through a knockout.
5. After wiring, conguring, and testing the
unit (see later sections), close the cover and
(optionally) secure it with two (supplied) self-
tapping screws.
SAE-1162 Duct Mount
Choose a mounting location in a straight section of
a return air duct. Mount at least 5 feet (or 7.5 duct
diameters) from corners and other items that may
cause disturbances in the air ow. Avoid areas prone
to vibration or rapid temperature change.
1. Cut a 1-1/8 or 1-1/4 inch hole in the duct for the
air sampling probe.
2. Insert the probe through the hole, align the unit
so that the duct air ow is parallel with the side
vent holes in the probe (air ows directly into
the probe holes), and mark the four enclosure
mounting holes.
3. Drill the four mounting holes (for screws) and
remove any debris from all holes.
4 . Insert the sampling probe into the duct.
5. Aach the unit to the ductwork by threading four
screws through the four holes on the outside of
the enclosure.
6. Remove the two cover screws (if installed),
release the latch, and swing open the cover.
7. Insert wiring through a knockout. After wiring a
duct sensor, ll the knockout hole with plumber’s
Mounting
145 mm
5.7"
101 mm
4"
114 mm
4.5"
89 mm
3.5"
ALARM
64 mm
2.5"
240 mm
9.5"
26 mm
1"
177 mm
7.0"
145 mm
5.7"
101 mm
4"
114 mm
4.5"
89 mm
3.5"
ALARM
64 mm
2.5"
SAE-1111/1112
SAE-1162
puy, caulk, or other sealant to prevent air
inltration from the conduit.
8. After wiring, conguring, and testing the
unit (see later sections), close the cover and
(optionally) secure it with two tapping screws.
Vista de pagina 0
1 2 3 4 5 6 7 8 9

Indice de contenidos

Pagina 1 - Installation Guide

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 1 Installation GuideInstallation GuideCarbon Monoxide (CO) Detectors SAE-1111/1112/1162 Mounting 1

Pagina 2 - CAUTION

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 2 Installation GuideUse 22 AWG shielded wiring for all connections. Do not locate device wires in

Pagina 3 - Operation

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 3 Installation GuideOperationWarm-Up Mode1. Verify that the detector is properly wired and all co

Pagina 4 - Configuration

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 4 Installation Guideswitch on the front cover (or activate the remote TEST input) when the CO leve

Pagina 5

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 5 Installation GuideWhen a value is changed, press the <SAVE> key to save it to memory and a

Pagina 6 - WARNING

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 6 Installation GuidePress <MENU>Relay 2 Hyst = 20 Use the <ROLL> key to scroll throug

Pagina 7

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 7 Installation GuidePress <MENU>ReCal Md Time = 1yr This is used to set the CO sensor recal

Pagina 8 - Calibration

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 8 Installation GuideNOTE: The sensor must be continuously powered for at least 1/2 hour prior to

Pagina 9 - Important Notices

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors 9 Installation Guide© 2014 KMC Controls, Inc. 717-019-55CKMC Controls, Inc.19476 Industrial Driv

Modelos relacionados SAE-1112 | SAE-1111 |

Comentarios a estos manuales

Sin comentarios