NetSensor Installation and Operation
Revision A 5
Motion sensor range 33 feet (10 meters)
Network cable preparation
Connecting a NetSensor to a controller requires a six-wire cable with
RJ-12 connectors on each end. KMC plenum-rated preassembled
cables are recommended. Cables made to length must meet the
following requirements:
◆ Cable length must be no longer than 75 feet (22.9 meters).
◆ Cable conductors must be no smaller than #24 AWG.
◆ Cable insulation must meet local building codes.
◆ Connectors must be appropriate for the cable in use and are
installed following the connector manufacturers instructions.
Cable details
55
°
10 m
32.8 ft
10 m
32.8 ft
X
0°
10 m
32.8 ft
10 m
32.8 ft
0°
46.5
°
Y
Comentarios a estos manuales