Procedure Detailed steps STE display
3 Set the primary VAV
terminal unit K-factor.
The K-factor is supplied by the manufacturer of
the VAV terminal unit. Typically it is on the label
with the unit airflow information.
1.
Press the or buttons to set the primary
K-factor.
2.
Press the
button to save the entry and
advance to the next function.
4 Set the secondary VAV
terminal unit K-factor.
Not used in all models.
The K-factor is supplied by the manufacturer of
the VAV terminal unit. Typically it is on the label
with the unit airflow information.
1.
Press the or buttons to set the secondary
K-factor.
2.
Press the
button to save the entry and
advance to the next function.
5 Set the mode of reheat
for the terminal unit.
Not used in all models.
1.
Press the or buttons to choose one of the
following reheat options.
None—Reheat is not enabled.
Staged—Enables staged reheat.
Modulating—The analog reheat output varies
from 0-10 volts DC.
Floating—The reheat outputs control a tristate
actuator.
Time proportional—Controls a thermal wax
valve with a 24-volt triac output.
2.
Press the
button to save the reheat option
and advance to the next function.
Procedure to set the box functions (continued)
Section 4: Configuring the controllers SimplyVAV
32 Revision E