Kmc-controls BAC-8007 Installation Guide Manual de usuario Pagina 68

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 88
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 67
loop is at 50%, the reheat output is On for 5 seconds and Off for 5 seconds. If
the Reheat loop is less than 10%, the reheat output remains at zero.
See the topic Time proportional reheat on page 53 for an application drawing.
Illustration 7–5 Time proportional reheat operation
Room temp increase
HTG SP-2F
HTG SPAN
loop %
0
100
10
HTG %
Reheat
Floating reheat
If the controller is configured for floating reheat, it controls two binary triac
outputs to drive the inputs of a tri-state actuator connected to a valve. If the
Reheat loop is less than 30%, the valve is driven closed. If the loop is greater
than 70%, the valve is driven open. If the loop is in between 30% and 70%, no
valve action is taken.
See the topic Floating reheat on page 54 for an application drawing.
Illustration 7–6 Floating reheat operation
HTG %
DRIVE
OPEN
DRIVE
CLOSED
loop %
0
100
70
Reheat
30
HTG SP
HTG SPAN
-2F
Room temp increase
NO ACTION
Section 7: Sequences of operation SimplyVAV
68 Revision E
Vista de pagina 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 87 88

Comentarios a estos manuales

Sin comentarios