Procedure Detailed steps STE display
6 Set the fan option.
Not used in all models.
1.
Press the or buttons to choose one of the
following fan options.
None—No fan is connected to the controller.
Series—The VAV unit includes a series fan.
Parallel—The VAV unit includes a parallel fan.
2.
Press the
button to save the fan option and
advance to the next function.
7 Set the damper direction
to close.
1.
Press the or buttons to which direction
to damper moves to close.
CCW—The actuator turns counterclockwise to
close the damper.
CW—The actuator turns clockwise to close the
damper.
2.
Press the
button to save the damper option
and advance to the next function.
8 Select a new
configuration function or
exit.
1.
Press the or buttons to select one of the
following:
STPT, FLOW, ADVC. or RSTR options
BACK to choose another configuration
function
EXIT to return to the temperature display.
2.
Press the
button to select the next function.
Procedure to set the box functions (continued)
SimplyVAV Section 4: Configuring the controllers
Revision E 33